IBEKO Power AB
Our goal is to always keep providing the world market with the most advanced test solutions for transformers, circuit breakers and batteries
- +1 800 599 8113
+46 70 0925 000 - +46 8 731 77 99
- support@dv-power.com
- sales@dv-power.com
- Box 1346
Lidingö, 181 25
Sweden
-
Product
Battery Capacity Tester
BLU-T Series
-
Battery load bank BLU-T is a powerful and lightweight solution designed for condition assessment of telecommunication and radio equipment backup supply. This instrument can perform the battery capacity test on battery strings such as Pb, Li-ion, Ni-Cd, and others. It tests battery strings with voltages in the range of 0,9 – 70,5 V DC. As a special feature, the BLU110T model enables capacity testing of single PB, Ni-based as well as Li cells (with current up to 100 A).The capacity test is conducted in an accurate, user-friendly way. Also, it is in accordance with battery testing standards: IEEE 450-2010, IEEE 1188-2005, IEEE 1106-2015, IEC 60896-11/22, and other relevant standards.BLU-T battery load bank enables setting the discharge current up to 350 A, with 0,1 A resolution. If higher currents are required, the BLU-T units can be connected in parallel, or BXL-T additional load units can be linked.The instrument offers a high power-to-weight ratio. BLU-T series has models starting from 12,8 kg / 28.2 lbs and up to 19,2 kW of power.A user can select one of three discharge modes: Constant current, Constant power, Constant resistance. Additionally, different battery duty cycles can be simulated using user-selectable discharge profiles.Discharge parameters can be monitored in real-time during the capacity test. A 4,3-inch touch screen shows overall battery voltage, discharge current, discharge test time and capacity during the entire test. Also, the capacity tester is compatible with DV-B Win software. A user can view a detailed numerical and graphical presentation of key parameters, and create reports in various formats.Testing can be carried out without disconnecting the battery from the service.
-
Product
Coil Analyzers & Power Supplies
-
Coil analyzers and power supply units are portable and lightweight devices intended for use in harsh switchyard and industrial environments. The typical application is switchgear and circuit breaker testing when substation battery is not connected or available. An advantage over substation battery is enabled testing in under-voltage and over-voltage conditions. Furthermore, the stable voltage outputs with a very low ripple (<0,5%) enable an analysis of the coil and motor current graphs recorded with circuit breaker analyzers from different vendors.SAT40AD, POB30AD, and POB40AD are unique devices in the market due to their dual purpose:Power supply for coils and spring-charging motorsTesting circuit breaker’s coils, motor, and auxiliary circuitAll DV Power coil analyzers and power supply units have four separate outputs for opening and closing coils.SAT40AD has two powerful motor outputs (AC and DC) which can withstand up to 40 A inrush current.POB30AD and POB40AD have DC motor output rated up to 30 A and 40 A respectively. With the use of motor outputs, POB and SAT can also be used as a power source or a temporary battery charger.SAT40A II series instruments can be controlled via PC. The DV-Win application software is used to control both SAT and CAT (Circuit Breaker Analyzers & Timers) devices at the same time, making a unique test system for switchgear and circuit breaker testing.
-
Product
Battery Extra Load Units
BXL Series
-
BXL is an extra load unit designed to be used with DV Power’s BLU series battery testers. However, this unit is a universal add-on device. Because of that, it is compatible, as an additional load, with any other discharge/capacity tester in the market.In case when discharge current exceeds the capacity of a single BLU device, BXL can increase the discharge capacity. There are no limitations on the number of extra load units that can be connected in parallel to the main battery tester.A system of BLU and BXL instruments enables performing the capacity test in an accurate, user-friendly way. Also, all instruments are in accordance with battery testing standards: IEEE 450-2010, IEEE 1188-2005, IEEE 1106-2015, IEC 60896-11/22, and other relevant standards.These units can be used on any type of battery string, such as lead-acid, Li-Ion, Ni-Cd, etc. They test battery strings with voltages in the range of 5,25 – 500 V DC. On the other hand, current up to 250 A can be discharged through the BXL internal structure.The instrument simulates a constant resistance load during the discharge test. Several resistances can be set for different battery nominal voltage levels. This makes BXL extremely flexible in selecting its load capabilities.
-
Product
Three-Phase Transformer Winding Resistance Meters
TWA Standard Series
-
When it comes to winding resistance measurement on three-phase power transformers and autotransformers, TWA Standard series offers some of the most technically advanced instruments with LCD display in the market. Both models are capable of testing six transformer windings with a one-time cable connection, as well as three-phase automatic transformer demagnetization. The stored magnetic energy is safely automatically discharged at the end of the test. The built-in tap changer control unit enables automated test mode, where the instrument operates the tap changer without operator input and records winding resistance results based on pre-selected stabilization criteria. This option makes the operator’s job significantly easier.Both models can output test currents from 5 mA to 25 A DC for the purpose of winding resistance measurement. TWA40D has a special test mode for checking the synchronization of on-load tap changers with three phases simultaneously tested in parallel, in which the total test current can rise to up to 40 A DC.TWA40D has additional advantages when it comes to non-intrusive tap changer analysis. The unique DVtest method enables checking the moving contacts of on-load tap changers during the transition, measuring the transition time, detecting open circuits, and many other types of faults. It is performed with 0.1 ms sampling rate, simultaneously with the measurement of tap changer motor current which helps with the detection of motor and mechanical issues. A special proprietary algorithm is used for testing tap changers connected through a built-in series (booster) transformer. The DVtest can be performed either on one phase or on three phases simultaneously. It can also be performed as an additional test simultaneously with the winding resistance test in all tap positions.An additional unique advantage of TWA40D is the capability of simultaneously testing the winding resistance of all three phases of a three-phase transformer (connected in a YN configuration). This can significantly shorten the total testing time – for example, it enables the operator to perform 33 measurements instead of 99 on a tap changer with 33 tap positions.The test leads for TWA three-phase transformer winding ohmmeters are interchangeable with the TRT turns ratio testers, which means that both sets of tests can be performed with a single test lead connection to the power transformer terminals.
-
Product
Micro-Ohmmeters
RMO-A Series
-
The RMO-A is a portable micro-ohmmeter designed for contact resistance measurements of switchgear during manufacturing, commissioning and maintenance stages. This micro-ohmmeter is widely used by medium and high-voltage circuit breakers manufacturers. Other typical applications are testing of disconnecting switches, high-current bus bar joints, cable splices, and different high-current links. It accurately measures not only in factory environments but also in high-induction fields and substationsThe RMO-A series contains 6 models, rated from 100 A (RMO100A) to 600 A (RMO600A). The RMO500A (formerly CPM500) is our best seller, with 500 A ripple-free current and weighs only 8 kg.Although placed in a very portable and lightweight metal housing, RMO-A micro-ohmmeters have very high output power capabilities. They can generate 600 A test current continuously for up to 20 s. You can test with current up to 100 A without rest time. High output voltage enables a wider measurement range at the highest test currents, as well as the use of thinner/longer test cables. For testing with 100 A, 20 m test leads can be provided with only 16 mm2 cross-section.RMO-A micro-ohmmeter generates a true DC ripple-free (less than 1 %) current with automatically regulated test ramps. During a test, the RMO-A ramps up with increasing current before measuring and decreasing current after the measurement. This significantly decreases magnetic transients and ensures great accuracy.An additional option is a built-in High Precision module suitable for measurement of very low resistances, ranges from 1 to 30 µΩ, with 0,01 µΩ resolution.These instruments can store up to 500 measurements in internal memory. A built-in thermal printer is available as an option.Our free DV Win software communicates with the RMO-A micro-ohmmeters via USB or RS232 interface. It allows you to run the test remotely from PC, as well as to download test results, analyze and generate fully configurable test reports.
-
Product
Software
DV-Win
-
An unique software application called DV-Win has been developed by DV Power as a tool compatible with all series of our instruments. Software automatically recognizes the device which is connected to a PC and activates appropriate form.
-
Product
Single-Phase Transformer Winding Resistance Meters
RMO-TW Series
-
RMO-TW series is perfect for winding resistance measurements of inductive objects. It is ideal for testing transformer windings (power transformers, distribution, autotransformers) and for on-load tap changer verification. In addition, any RMO-TW transformer ohmmeter & tap changer analyzer can also perform transformer demagnetization.The series contains 4 models, with maximal test currents from 10 A (RMO10TW) to 50 A (RMO50TW). They are fitted in a portable and lightweight metal housing.All transformer ohmmeters from RMO-TW series generate a true DC ripple-free current with automatically regulated measurement and discharging circuit. The injection of current and discharge of energy from the test object are automatically regulated.Three independent channels enable testing of three windings in series. Consequently, this enables measurements of winding resistance in every tap position of an on-load tap changer without discharging between the tests.DV-Win software enables control and observation of the test process, as well as saving and analyzing the results on a PC. It provides a test report, arranged in a selectable form as an Excel spreadsheet, PDF, Word, or ASCII format. Additionally, DV-Win measures and calculates the OLTC transition time, the ripple and the winding resistance for each tap changing operation. The software can also perform the calculations necessary for the “Heat Run” test. Finally, a user can export all results in the form of a report.
-
Product
Electrical Safety Test Equipment
-
Making a product “safe” requires an understanding of “hazards” that exist in each electrical product. Electrical shock is one of the four fundamental hazards. Because of that, it must be a part of any product electrical safety evaluation. Even though a product requires an electrical power source and uses electrical or electronic components, it should not present an electrical shock hazard to the user.Ground bond or earth continuity testing prevents electrical shock hazards. Similarly to a fault to earth, test instruments generate a high current. The standard requires that the resistance between protective earth and any conductive surface on the equipment does not exceed 0,1 Ohm. The test is performed by applying a DC current between the conductive surface and protective earth. By measuring the voltage drop, it calculates the resistance.RMO-E instruments are ideal for testing the protective bonding (grounding) of equipment following the standard IEC 61010-1. Applying current up to the value of 100 A and the ability to provide in the Contin menu (continuous operation) test current for the pre-set test duration (equal or exceeding 1 min) gives a user a possibility to easily check the protective bonding/grounding of the equipment. The full load voltage of 12 V assures proper measurement and accurate result. Finally, an instrument displays pass/fail classification according to user-preset parameters.
-
Product
Battery Supervisors
-
DV Power manufactures ideal tools for maintenance, troubleshooting and performance tests on stationary batteries.Capacity testing is performed in order to detect which cells in the string should be replaced by measuring a cell voltage, temperature, inter-cell connection voltage, and specific gravity.IEEE standards for stationary battery applications also stipulate measuring these key parameters during periodic battery inspections.DV Power provides two types of instruments:BVS series – for automated monitoring of battery parametersBVR series – for manual monitoring of battery parametersIn contrast to BVS, BVR instruments can be used for the transfer of electrolyte specific gravity measurements from a density meter (DMA35) via Bluetooth. This provides a more extensive analysis of each cell in the tested battery string.
-
Product
Turns Ratio Testers
TRT Standard Series
-
When it comes to choosing a transformer turns ratio tester, TRT Standard series offers some of the most advanced instruments with LCD display out in the market. Each model measures transformer excitation current and phase shift performs automatic vector group detection and magnetic balance on three-phase transformers and three-phase autotransformers. Furthermore, they have a built-in true three-phase power source. Because of that, TRT Standard instruments can test transformers with special configurations, such as phase-shifting, rectifier, arc-furnace, traction transformers, etc.The instruments can output test voltages from 1 V AC to 250 V AC, depending on the chosen model. High test voltage of 250 V AC provides more accurate turns ratio testing compared to other turns ratio testers on the market and extremely low test voltage of 1 V AC enables turns ratio verification of current transformers.TRT Standard series consists of:TRT03 Models (TRT03A, TRT03B, TRT03C) – single-phase voltage up to 100 VTRT3x Models (TRT30A, TRT30B, TRT30C, TRT33A, TRT33B, TRT33C) – single and true three-phase voltage up to 100 VTRT63 Models (TRT63A, TRT63B, TRT63C) – single and true three-phase voltage up to 250 VMore about models differences can be found under the downloads tab, in brochures and comparison sheets.A user can create test templates using the DV Win software and store them in the PC’s memory for later use when in the field.TRT Standard series models have a built-in tap changer control unit. Consequently, it enables remote control of an on-load tap changer (OLTC) directly from the tester. In order to make the most out of this feature, the DV-Win software can be programmed to do everything automatically – running turns ratio tests, changing OLTC tap positions and saving results. This option, especially in combination with test templates, significantly facilitates and shortens the turns ratio testing time.
-
Product
Turns Ratio Testers
TRT Advanced Series
-
TRT Advanced series is the newest DV Power solution for transformer turns ratio measurement. Besides its main application, each turns ratio tester from this series also measures transformer excitation current and phase shift. Furthermore, all models perform automatic vector group detection and magnetic balance on three-phase transformers and three-phase autotransformers. They have a built-in true three-phase power source. For that reason, they can test transformers with special configurations, such as phase-shifting, rectifier, arc-furnace, traction transformers, etc.The instruments can output test voltages from 1 V AC to 500 V AC, depending on the model. With the highest test voltage 500 V AC, TRT500 provides the most accurate turns ratio testing of power transformers used in power generation and transmission. The output test voltage of TRT500 can be boosted to 5 kV AC using the external CVT20 extension transformer. This application is specially designed for testing turns ratio of capacitive voltage transformers. The other three models, TRT400, TRT250, and TRT100 can output up to 400 V, 250 V, and 170 V respectively. The low test voltage of 1 V AC enables turns ratio verification of current transformers.TRT500 is equipped with a large 10.1” graphical touch screen display. Other models, (TRT400, TRT250, TRT100) have 7” graphical touch screen display. Besides making the interface much more user-friendly compared to older turns ratio testers, it also brings certain options that were previously available only with DV-Win software. The most important are test templates and automatic test mode. Users can simply create test templates, store them in the instrument’s memory, and load when in the field with just a few clicks.This turns ratio test set, as well as all other DV Power turns ratio testers, has a built-in tap changer control unit. It enables remote control of an on-load tap changer (OLTC) directly from the instrument. In order to make the most out of this feature, the instrument can be programmed to do everything automatically – running turns ratio tests, changing OLTC tap positions, and saving results. This option, especially in combination with test templates, significantly facilitates and shortens the turns ratio testing time. Automatic test mode minimizes human errors, which makes the measurement more reliable.
-
Product
Battery Capacity Testers|Discharge Testers
-
DV Power offers a wide range of battery capacity testers to meet specific customer needs. All of them are portable, powerful and most of all universal. Any battery string, such as lead-acid, lithium-ion, nickel-cadmium based and others, with voltages in the range of 0,9 – 800 V DC can be tested in an accurate, user-friendly way.The capacity test is carried out following the battery testing standards: IEEE 450-2010, IEEE 1188-2005, IEEE 1106-2015, IEC 60896-11/22, and other relevant standards.BLU battery testers enable setting the discharge current up to 350 A, with 0,1 A resolution. If higher currents are required, several units can be connected in parallel, or BXL additional load units can be used. Discharge parameters can be monitored in real-time during the capacity test. Overall battery voltage, current, elapsed test time and capacity will be presented during the entire test on a touch screen display.